EJA130E High Static Differential Pressure Transmitter is mainly for high static pressure differential pressure measurement, static pressure up to 32Mpa, with traditional process connection, DP measure range 0-100kpa and 0-500kpa, only stainless type wetted part material selectable. FM, ATEX, Canadian Standards Association (CSA), IECEx and NEPSI Explosion proof Approval are selectable for different of design standard and local regulations.
For FM Explosion proof Approval with order code FF1: Applicable Standard: FM3600, FM3615, FM3810, ANSI/NEMA 250 Explosion proof for Class I, Division 1, Groups B, C and D, Dust-ignition proof for Class II/III, Division 1,Groups E, F and G, in Hazardous locations, indoors and outdoors (NEMA TYPE 4X)"FACTORY SEALED, CONDUIT SEAL NOT REQUIRED."Temperature class: T6, Ambient Temp.: –40 to 60℃ (–40 to 140℉)
For FM Intrinsically safe Approval with order code FS1:Applicable Standard: FM3600, FM3610, FM3611, FM3810 Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1,Groups E, F & G and Class III, Division 1, Class I, Zone 0, in Hazardous Locations, AEx ia IIC Non-incendive for Class I, Division 2, Groups A, B, C & D, Class II, Division. 2, Groups F & G, Class I, Zone 2, Group IIC, in Hazardous Locations. Enclosure: "NEMA TYPE 4X", Temp. Class: T4, Ambient Temp.: –60 to 60℃ (–75 to 140℉) Intrinsically Safe Apparatus Parameters [Groups A, B, C, D, E, F and G] Vmax=30 V, Imax=200 mA, Pmax=1 W, Ci=6 nF, Li=0μH, [Groups C, D, E, F and G] Vmax=30 V, Imax=225 mA, Pmax=1 W, Ci=6 nF, Li=0μH.
For ATEX Flameproof Approval with order code KF22: Applicable Standard: EN 60079-0:2009, EN 60079-1:2007, EN60079-31:2009 Certificate: KEMA 07ATEX0109 XII 2G, 2D Ex d IIC T6...T4 Gb, Ex tb IIIC T85℃ Db IP6X; Degree of protection: IP66/IP67; Ambient Temperature (Tamb) for gas-proof : T4; –50 to 75℃ (–58 to 167℉), T5; –50 to 80℃ (–58 to 176℉), T6; –50 to 75℃ (–58 to 167℉), Max. process Temp. for gas-proof (Tp): T4; 120℃ (248℉), T5; 100℃ (212℉), T6; 85℃ (185℉); Max. surface Temp. for dust-proof: T85℃ (Tamb: –30 to 75℃, Tp: 85℃).
For ATEX Intrinsically safe Approval KS21: Applicable Standard: EN 60079-0:2009, EN 60079-11:2007, EN 60079:2012, EN60079-26:2007, EN 61241-11:2006, Certificate: DEKRA 11ATEX0228 XII 1G, 2D Ex ia IIC T4 Ga, Ex ia IIIC T85℃ T100℃ T120℃ Db; Degree of protection: IP66/IP67, Ambient Temp. (Tamb) for EPL Ga: –50 to 60℃ (–58 to 140℉) Maximum Process Temp. (Tp) for EPL Ga:120℃; Electrical data: Ui=30 V, Ii=200 mA, Pi=0.9 W, Ci=27.6 nF, Li=0 μH, Ambient Temp. for EPL Db: –30 to 60℃ ; Max. surface Temp. for EPL Db: T85℃ (Tp: 80℃), T100℃ (Tp: 100℃), T120℃ (Tp: 120℃)
2. Measuring Span & Range limits
Measurement Span/Range |
kPa |
inH2O (/D1) |
Mbar (/D3) |
mmH2O (/D4) |
||
M |
Span |
1 to 100 |
4 to 400 |
10 to 1000 |
100 to10000 |
|
Range |
-100 to 100 |
-400 to 400 |
-1000 to1000 |
-10000 to10000 |
||
E |
Span |
5 to 500 |
20 to 2000 |
50 to 5000 |
0.05 to 5kgf/cm2 |
|
Range |
-500 to 500 |
-2000 to 2000 |
-5000 to 5000 |
-5 to 5kgf/cm2 |
3. Wetted Parts Materials
Wetted parts |
Cover flange and process connector |
Capsule |
Capsule gasket |
Vent/Drain plug |
S |
ASTM CF-8M |
Hastelloy C-276 (Diaphragm) F316L SST, 316L SST (Others) |
Teflon-coated 316L SST |
316 SST |
4. Model and suffix codes
Main Code |
Suffix Codes |
Description |
|||||||||
EJA130E |
Differential pressure transmitter |
||||||||||
Output signal |
-D |
4 to 20 mA DC with digital communication (BRAIN protocol) |
|||||||||
-J |
4 to 20 mA DC with digital communication (HART 5/HART 7 protocol) |
||||||||||
-F |
Digital communication (FOUNDATION Fieldbus protocol) |
||||||||||
-G |
Digital communication (PROFIBUS PA protocol) |
||||||||||
-Q |
Low Power, 1 to 5 V DC with digital communication (HART 7 protocol) |
||||||||||
Measurement span (capsule) |
M |
http://www.ahjianlong.com/